Sizes
NOTE: The Integrity and Insulation rating of this product is limited to the capability of the surrounding substrates, we do not permit the use of this product against combustible cladding.
Rainbar
Length (in mm)
Depth (in mm)
Thickness (in mm)
Maximum Opening
1200mm
105mm
15mm
100mm
Accessories
Product
Size
Use
Rainbar Spike
Small
Fixing
Large
V-Lock
Z Clip V-Lock
340 x 30 x 1 mm
For fixing to non-fire-rated cladding
Z Clips
300 x 30 x 0.8 mm
Use Firetherm Rainbar Pro within rain screen cladding for up to 60 minutes of fire protection in cavities. This cavity fire barrier helps maintain compartment lines to the exterior of the building envelope, lying dormant until attacked by fire, when its intumescent-coated facing expands to seal up gaps, preventing the spread of smoke and fire to up to an hour.
Comprising of an engineered, powder-coated and galvanized steel carrier, the carrier retains a high-pressure graphite manipulated intumescent composite that expands in a fire to seal a maximum 100mm gap. Rainbar Pro is quick and easy to install on-site and is extremely durable, giving a service life equal to that of the building with no requirement for maintenance, unless physically damaged. The simple fixing system allows for free-flow air movement and the drainage of moisture, preventing mould growth and dampness within the cavity.
Features
Ultra-slim flange and body design ensures easy installation in awkward situations
Fully tested at BM TRADA up 60 minutes integrity and insulation
No interruption of cavity ventilation
Allows free airflow, preventing mould and dampness
Intumescent facing can expand to seal gaps of up to 100mm
Installation
For all gap widths between 40 and 100 mm.
Maximum air space 85 mm (based on 100 mm cavity).
Minimum air space 25 mm (based on 40 mm cavity).
Reduction of free flow air space can be accommodated by design specification.
NOTE: The Integrity and Insulation rating of this product is limited to the capability of the surrounding substrates, we do not permit the use of this product against combustible cladding.
Fixings
Fixing centres may not exceed 400 mm.
Joint to joint fixing centres may not exceed 400 mm and may not be less than 100 mm from the joint.
All pieces exceeding 600 mm require a minimum of 3 fixings.
Minimum fixings cut pieces 300 mm - 600 mm = 2 (100 mm from joints). Smaller pieces always require two fixings at equal distance from the centre line.
Fixings should be located centrally through the depth of the product +/- 5mm to the centre line.
Fire Testing
Tested at Exova BM Trada to BS 476 Pt 20-22 and BS EN 1366-4
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contactedto obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditionsand should be applied only by an individual with the necessary expertise and experience.We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.
Firetherm Rainbar Pro is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
An extensive range of accessories and ancillary products for use with Nullifire (Firetherm) systems, helping the installation and application of firestopping products. Refer below to see the full range. More Information Delivery Info