Protecta FR Foam, part of the Protecta Firestopping range, maintains fire resistance in walls by filling linear gaps in concrete and masonry walls, with excellent adhesion to most materials used in construction and excellent durability during service once cured.
Protecta FR Foam is designed to maintain the fire resistance in walls by filling linear gaps in concrete and masonry walls. Supplied as a single component polyurethane foam that cures by moisture absorption, it has excellent adhesion to most materials used in construction with excellent durability during service once cured.
FR Foam also has excellent thermal properties (0.0354 W/mK).
Reference | Product Name | Size | Colour | Pack Size |
---|---|---|---|---|
P166 | Protecta FR Foam | 750ml (Gun Grade) | Grey | Box of 12 |
Installation
Sealing masonry or concrete walls ≥ 150MM
Joint type (Max width) | Installation (Min seal depth) | Joint type Classification |
---|---|---|
Horizontal joint ≤ 20mm | Single sided ≥ 150mm (1) | EI 180-H-X-F-W 20 |
Horizontal joint ≤ 20mm | Single sided ≥ 140mm (2) | EI 240-H-X-F-W 20 |
Vertical joint ≤ 20mm | Single sided ≥ 150mm (1) | EI 60-V-X-F-W 20 |
Vertical joint ≤ 20mm | Single sided ≥ 140mm (2) | EI 240-V-X-F-W 20 |
Description | Sound reduction |
---|---|
Single sided seal ≥ 50mm depth & ≤ 30mm width | 61 dB RW |
Same or higher sound reduction will be achieved with greater depth, double sided or with backing material. The sound insulation value is only valid for the foam and not for other elements in the building construction. The sound insulation has been tested by the accredited laboratory BM Trada in Great Britain according to EN ISO 10140-2. Test report is available upon request.
This Installation Instruction is based on the product’s European Technical Assessment, issued in accordance with regulation (EU) No 305/2011, on the basis of ETAG 026-2 and 3, edition 2011, used as European Assessment Document (EAD).
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions . We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.
Protecta FR Foam is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT