Protecta FR Damper fire proofs ventilation ducts that pass through fire-rated walls & floors, preventing spread of fire & smoke both surrounding & inside ducts. The steel casing contains horizontal steel blades treated with a technically advanced heat expanding graphite, closing off the damper in fire.
Protecta FR Damper, part of the Protecta Firestopping range, fire proofs ventilation ducts where they penetrate fire rated constructions such as fire compartments in floors and fire walls, preventing the passage of fire and smoke both surrounding and inside the ventilation duct.
It consists of a steel casing containing horizontal steel blades treated with a technically advanced heat expanding graphite which closes off the whole damper in a fire. The aperture surrounding the dampers are fire sealed with Protecta FR Board in walls and Protecta EX Mortar in floors.
The damper can be installed in the fire seal and the ventilation ducting attached or the damper can be connected to the ducting and then fire sealed.
The aperture where the ducts pass through can include one or multiple ventilation ducts. One can also pass through other technical services such as cables, cable trays and pipes within the same aperture.
Reference | Product Name | Size | Colour | Weight |
---|---|---|---|---|
P195 | Protecta FR Damper | 63mm Diameter | Grey | 0.51 kg |
P196 | Protecta FR Damper | 80mm Diameter | Grey | 0.68 kg |
P197 | Protecta FR Damper | 100mm Diameter | Grey | 1.24 kg |
P198 | Protecta FR Damper | 125mm Diameter | Grey | 1.57 kg |
P199 | Protecta FR Damper | 160mm Diameter | Grey | 2.35 kg |
P200 | Protecta FR Damper | 200mm Diameter | Grey | 3.36 kg |
P201 | Protecta FR Damper | 250mm Diameter | Grey | 3.90 kg |
P202 | Protecta FR Damper | 315mm Diameter | Grey | 7.36 kg |
P203 | Protecta FR Damper | 400mm Diameter | Grey | 11.28 kg |
P204 | Protecta FR Damper | 500mm Diameter | Grey | 14.60 kg |
P205 | Protecta FR Damper | 630mm Diameter | Grey | 20.90 kg |
P206 | Protecta FR Damper | 800mm Diameter | Grey | 32.24 kg |
P207 | Protecta FR Damper | 1000mm Diameter | Grey | 49.80 kg |
P208 | Protecta FR Damper | 1250mm Diameter | Grey | 74.00 kg |
The length of the dampers in the table are 150mm plus overlap/ connection for the ventilation ducts. Longer and shorter dampers can be manufactured on request.
Protecta FR Damper for rectangular ducts are manufactured to precise measurements, and are not standard goods.
Contact our sales team on 0113 2455450 or [email protected] to discuss your fire-stopping projects and requirements.
Appearance | Ready manufactured in steel and graphite |
BREEAM | Approved, EC1 PLUS on all fire seals |
Interior climate, installed | Z 2 : Relative air moisture up to 85% and temperatures between 5 and 40°C |
Trigger-temperature in fire | 100°C |
Temperature, full closure | 160°C |
Time to full closure | From 50 seconds to 2 minutes |
Expansion rate graphite | 15.5 to 17 |
Density graphite | 2.6 kg per ltr |
Thickness graphite | 1.6 mm |
Leakage classification | Class C according to EN 1751 (circular) |
Free air opening | Between 84.2% and 85.4% |
Pressure in fire | FR Damper resists minimum 300Pa |
Standard for connections | EN 1506:2007 |
Standard for fire testing | EN 1366-12:2014 & EN 1363-1:2012 |
Standard for aerodynamics | EN 1751:2014 |
Standard for sound levels | EN ISO 5135:1998 |
Storage | In temperatures between 5°C and 30°C |
Life span | Under normal conditions; 50 years + |
Installation temperature | +5°C to +50°C |
Colour | Galvanized steel with section of red colour to identify placement of the fire seal |
Construction | Description | Classification |
---|---|---|
Flexible and rigid walls with thickness ≥ 100mm | ≤ Ø 400mm FR Damper/duct with ≥ 200mm stone wool mat on both sides | EI 120 (E 120) |
≤ Ø 1250mm FR Damper/duct with ≥ 500mm stone wool mat on both sides | EI 60 (E 90) | |
≤ 600mm high x 1000mm wide FR Damper/duct with ≥ 500mm stone wool mat on both sides | EI 120 (E 120) | |
≤ 1200mm high x 1700mm wide FR Damper/duct with ≥ 500mm stone wool mat on both sides | EI 90 (E 90) | |
Rigid floors with thickness ≥ 150mm | ≤ Ø 400mm FR Damper/duct with ≥ 150mm stone wool mat on top side | EI 120 (E 180) |
≤ Ø 1000mm FR Damper/duct with ≥ 500mm stone wool mat on top side | EI 90 (E 90) | |
≤ 600 x 1000mm FR Damper/ duct with ≥ 500mm stone wool mat on top side | EI 60 (E 90) | |
≤ 1000 x 1000mm FR Damper/ duct with ≥ 500mm stone wool mat on top side | EI 90 (E 90) |
The stone wool mat described is with thickness ≥ 30mm and density ≥ 80kg/m³ with or without aluminium foil, attached according to the products installation instructions.
A combined close in and pull out solution prevents spread of fire by closing off the fire inside the fire compartment, using the ventilation system outside the area of the fire to pull out any smoke that filters out through the fire compartments constructions.
Protecta FR Dampers have to be used in all ventilation duct penetrations in fire compartments and fire walls, closing off the fire compartment but not in the parts of the building that are not on fire. For the principle to work effectively it is recommended that the ventilation unit is protected with a battery backup and a by-pass of the filters so that the smoke from the fire does not blind them.
When using Protecta FR Dampers the ventilation ducts do not need to be fully insulated.
Tests conducted on Protecta FR Damper to determine dust formation inside the damper show that dust does not collect inside the damper, and no more than in any other components in the ventilation system. The dust has a tendency to be blown through the dampers as long as the ventilation system is in constant operation and installed in normal indoor environments (Z 2).
It is recommended that the ventilation system is designed and cleaned according to local regulations and building codes to provide access for inspections and cleaning, along with the frequency of these cleaning routines. Protecta FR Damper can easily be cleaned using a vacuum cleaner if this should be needed. Ducts from kitchens and similar, where there is the risk of grease and high humidity, must be fitted with grease filters or similar that are cleaned at fixed frequencies.
The maximum size of an aperture is 1200 x 2400mm in floors and 1500mm height x 2400mm width or 1200mm height x unlimited width in walls. An aperture can include several services, and they may also include a combination, e.g. cables, cable trays and pipes.
The minimum permitted separation between adjacent seals/ apertures is 200mm. Services should be a minimum of 25mm from seal edges. Services within the system Protecta fire seal do not require a minimum separation, except when pipes where combustible pipe insulation penetrates the seal and plastic pipe penetrations which should be a minimum of 30 mm from other services in the aperture. There must be sufficient distance between two ventilation ducts so that the fire seal can be constructed as stated in the installation instructions.
Flexible walls must have a minimum thickness of 100mm and comprise steel studs or timber studs*** lined on both faces with minimum 2 layers of 12.5mm thick boards.
Rigid walls must have a minimum thickness of 100mm and comprise concrete, aerated concrete or masonry, with a minimum density of 650 kg/m³.
Rigid floors must have a minimum thickness of 150mm and comprise aerated concrete or concrete with a minimum density of 650 kg/m³.
The supporting construction must be classified in accordance with EN 13501-2 for the required fire resistance period.
***Timber studs: no part of the penetration seal may be closer than 100mm to a stud, and minimum 100mm of insulation of class A1 or A2 according to EN 13501-1 must be provided within the cavity between the penetration seal and the stud.
Description | Sound Classification |
---|---|
Protecta FR Board in wall | 55 dB |
Protecta EX Mortar in floor | 64 dB |
The sound insulation values are valid for the fire seal only and not any other components in the construction, as for instance the ventilation ducts.
Protecta products has been tested at BM Trada (UKAS accredited); according to EN ISO 10140-2:2010.
Protecta FR Dampers are fitted with high quality gaskets in circular ducts, and are tested according to EN 1751 to the highest possible class C for all sizes. Testing was conducted at BRE’s accredited laboratory and test reports can be provided upon request.
Case leakage classification for rectangular dampers is dependent on which locking mechanism is chosen, and the classification will be the same as the classification of the locking mechanism used. Polyseam can deliver dampers with most common types of locking mechanisms that are available in the marketplace.
Protecta EX Mortar has been subject to concentrated load and impact tests in floors according to ETAG 026-2 and EOTA TR001 Clause 2. The tests were conducted on the minimum allowed cast depth of 100mm.
According to the loading limits in the table below, reinforcement is not necessary, however it is highly recommended that the edges of the aperture are brushed free of any dust or loose particles and that any contamination is washed away using clean water. Moistening the edges well before casting will improve adhesion.
Protecta EX Mortar should not be cast in surface treated concrete. The mortar must be mixed to a thick but fluid mass at a rate of approx. 2 parts of powder to 1 part water. Maximum loadbearing performance will be achieved 28 days after casting.
Test results:
Test in 1500x1000mm frame | Results |
---|---|
Soft body impact, serviceability | 500Nm |
Soft body impact, safety in use | 700Nm |
Hard body impact, serviceability | 6 Nm |
Hard body impact, safety in use | 10 Nm |
Concentrated load to ETAG 26-2 | 15 kN |
Installation Instructions in Flexible Walls
Installation Instructions in Rigid Walls
Installation Instructions in Rigid Floors
Refer to the Product Data Sheet for data tables and line graphs.
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions . We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.
Protecta FR Damper is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT