Pyroplex CE Marked Pipe Wraps, specifically designed to reinstate the fire performance of compartment walls or floors penetrated with plastic flammable pipes used in soil, waste and drainage applications.
Ref | Item | Availability |
---|---|---|
PPW55-2H | PYROPLEX 2 hour pipe wrap 55mm | In Stock |
PPW82-2H | PYROPLEX 2 hour pipe wrap 82mm | In Stock |
PPW110-2H | PYROPLEX 2 hour pipe wrap 110mm | In Stock |
PPW160-2H | PYROPLEX 2 hour pipe wrap 160mm | In Stock |
PPW55-4H | PYROPLEX 4 hour pipe wrap 55mm | In Stock |
PPW82-4H | PYROPLEX 4 hour pipe wrap 82mm | In Stock |
PPW110-4H | PYROPLEX 4 hour pipe wrap 110mm | In Stock |
PPW125-4H | PYROPLEX 4 hour pipe wrap 125mm | 2-3 weeks |
PPW160-4H | PYROPLEX 4 hour pipe wrap 160mm | In Stock |
Pyroplex CE Marked Pipe Wraps have been specifically designed to reinstate the fire performance of compartment walls or floors penetrated with plastic flammable pipes used in soil, waste and drainage applications. The active element contained is specifically formulated to close and seal the aperture during the decomposition stage of the flammable service, creating a highly effective fire resistant barrier to minimise the propagation and permeation of hot gases into the adjacent compartment.
Pyroplex CE Marked Pipe Wraps have been tested in accordance with EN 1366-3 Penetration Seals, with a fire classification in accordance with EN 13501-2. Pyroplex CE Marked Pipe Wraps are assessed against EEC directive 305/2011 Article 29, ETA 12/0351. National UK certification in accordance with Certifire TS03 under certificated number CF 635.
Pyroplex CE Marked Pipe Wraps have been specifically designed to prevent the passage of fire and hot gases through:
Product Code | Recommended Pipe Diameter (mm) (min - maximum) |
---|---|
PPW55-2 | 53 - 58 |
PPW82-2 | 80 - 84 |
PPW110-2 | 108 - 113 |
PPW160-2 | 158 - 162 |
Product Code | Size |
---|---|
PPW55-4H | PYROPLEX 4 hour pipe wrap 55mm |
PPW82-4H | PYROPLEX 4 hour pipe wrap 82mm |
PPW110-4H | PYROPLEX 4 hour pipe wrap 110mm |
PPW125-4H | PYROPLEX 4 hour pipe wrap 125mm |
PPW160-4H | PYROPLEX 4 hour pipe wrap 160mm |
Other sizes available on request - contact our technical team with your requirements on 0113 2455450 (option 2) or send a message to [email protected].
Note: Diameter hole in wall or floor for guidance only.
Pyroplex 200 series wraps are now available in an extended range of sizes, suitable for a wide range of pipe diameters, pipe materials and can be used for a range of pipe thicknesses. To fit, simply wrap the pipe wrap around the service, secure using adhesive tab and slide the product into the cavity to the required depth. The annular gap between the pipe and the supporting construction can be reinstated as required.
Part no. | Pipe material | Pipe wall thickness (mm) | Hole Ø (mm) | Orientation | Fire classification WF174256/C |
---|---|---|---|---|---|
PPW55-2H | PVC-u | 3.2 | 70 | Wall | EI 120 - u/c |
PVC-u | 3.2 | Floor | |||
PPW82-2H | PVC-u | 3.2 | 98 | Wall | EI 120 - u/c |
PVC-u | 3.2 | Floor | |||
PPW110-2H | PVC-u | 3.2 | 130 | Wall | EI 120 - u/c |
PVC-u | 3.2 | Floor | |||
PPW160-2H | PVC-u | 3.2 | 190 | Wall | EI 120 - u/c |
PVC-u | 3.2 | Floor |
Table 1 – Floor penetrations tested to EN 1366-3 – Refer to WF Report No: 384250
PVC –U pipes according to EN 1329-1, EN 1453-1 or EN 1452-1 are valid for pipes made from PVC-U according to EN 1329-1, EN 1453-1 and EN 1452-1, including pipes made from PVC-C according to EN 1566-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
48.30mm - 50mm (nominal OD) | 3.70 - 5.10 | U/C - Floor | EI 120 |
160mm | 6.20 - 9.50 | U/C - Floor | EI 120 |
Table 2 – Floor penetrations tested to EN 1366-3 – Refer to WF Report No: 384250
PE-HD pipes according to EN 1519-1 or EN 1266-1 are valid for pipes made from PE according to EN 12201, EN 1519-1 and EN 12666-1.
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
50mm (nominal OD) | 3.00 - 4.60 | U/C - Floor | EI 120 |
160mm | 4.90 - 9.50 | U/C - Floor | EI 120 |
Table 3 – Floor penetrations tested to EN 1366-3 – Refer to WF Report No: 384250
PP pipes
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
50mm | 2.00 - 4.60 | U/C - Floor | EI 120 |
160mm | 4.90 - 9.10 | U/C - Floor | EI 120 |
Table 4 – Floor penetrations tested to EN 1366-3 – Refer to WF Report No: 384250
PP pipes according to DIN4102-B2
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
50mm | 2 | U/C - Floor | EI 120 |
58mm | 4 | U/C - Floor | EI 120 |
160mm | 5.3 | U/C - Floor | EI 90 |
160mm | 4.3 | U/C - Floor | EI 120 |
Table 5 – Floor penetrations tested to EN 1366-3 – Refer to WF Report No: 394147
PVC-U pipes according to EN 1329-1, EN 1453-1 or EN 1452-1 are valid for pipes made from PVC-U according to EN 1329-1, EN 1453-1 and EN 1452-1, including pipes made from PVC-C according to EN 1566-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
90mm | 3.20 - 5.40 | U/C - Floor | EI 120 |
Table 6 – Floor penetrations tested to EN 1366-3 – Refer to WF Report No: 394147
PE-HD according to EN 1519-1 or EN 12666-1 are valid for pipes made from PE according to EN 12201, EN 1519-1 and EN 12666-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
90mm | 2.80 - 8.20 | U/C - Floor | EI 120 |
Table 7 – Floor penetrations tested to EN 1366-3 – Refer to WF Report No: 394147
PP pipes according to B5174-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
90mm | 2.80 - 8.20 | U/C - Floor | EI 120 |
Table 8 – Wall penetrations tested to EN 1366-3 – Refer to WF Report No: 384251
PVC-U pipes according to EN 1329-1, EN 1453-1 or EN 1452-1 are valid for pipes made from PVC-U according to EN 1329-1, EN 1453-1 and EN 1452-1, including pipes made from PVC-C according to EN 1566-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
48.3mm-50mm (nominal OD) | 3.70 - 5.10 | U/C - Wall | EI 120 |
160mm | 6.20 - 9.50 | U/C - Wall | EI 120 |
Table 9 – Wall penetrations tested to EN 1366-3 – Refer to WF Report No: 384251
PE-HD according to EN 1519-1 or EN 12666-1 are valid for pipes made from PE according to EN 12201, EN 1519-1 and EN12666-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
50mm | 3.00 - 4.60 | U/C - Wall | EI 120 |
160mm | 4.90 - 9.5 | U/C - Wall | EI 120 |
Table 10 – Wall penetrations tested to EN 1366-3 – Refer to WF Report No: 384251 PP pipes
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
50mm | 2.00 - 4.60 | U/C - Wall | EI 120 |
160mm | 4.90 - 9.10 | U/C - Wall | EI 120 |
Table 11 – Wall penetrations tested to EN 1366-3 – Refer to WF Report No: 384251
PP pipes according to DIN4102-B2
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
50mm | 2 | U/C - Wall | EI 120 |
50mm | 4 | EI 120 | |
160mm | 4.3 | U/C - Wall | EI 120 |
160mm | 5.3 | U/C - Wall | EI 120 |
EI 60 |
Table 12 – Wall penetrations tested to EN 1366-3 – Refer to WF Report No: 394147
PVC-U pipes according to EN 1329-1, EN 1453-1 or EN 1452-1 are valid for pipes made from PVC-U according to EN 1329-1, EN 1453-1 and EN 1452-1, including pipes made from PVC-C according to EN 1566-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
90mm | 4.00 - 5.40 | U/C - Wall | EI 120 |
Table 13 – Wall penetrations tested to EN 1366-3 – Refer to WF Report No: 384251
PE-HD according to EN 1519-1 or EN 12666-1 are valid for pipes made from PE according to EN 12201, EN 1519-1 and EN 12666-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
90mm | 2.80 - 8.20 | U/C - Wall | EI 120 |
Table 14 – Wall penetrations tested to EN 1366-3 – Refer to WF Report No: 384251
PP pipes according to B5174-1
Pipe diameter | Pipe wall thickness (mm) | Orientation - end condition | Classification |
---|---|---|---|
90mm | 2.80 - 8.20 | U/C - Wall | EI 120 |
Part no. | Pipe material | Pipe wall thickness (mm) | Hole Ø (mm) | Orientation | Fire classification WF174256/C |
---|---|---|---|---|---|
PPW55-2H | PVC-u | 3.2 | 70 | Wall | EI 240 - u/c |
PVC-u | 3.2 | Floor | EI 120 - u/c | ||
PPW82-2H | PVC-u | 3.2 | 98 | Wall | EI 240 - u/c |
PVC-u | 3.2 | Floor | EI 240 - u/c | ||
PPW110-2H | PVC-u | 3.2 | 130 | Wall | EI 120 - u/c |
PVC-u | 3.2 | Floor | EI 120 - u/c | ||
PPW125-4 | PVC-u | 3.2 | 155 | Wall | EI 120 - u/c |
PVC-u | 3.2 | Floor | EI 180 - u/c | ||
PPW160-2H | PVC-u | 3.2 | 190 | Wall | EI 120 - u/c |
PVC-u | 3.2 | Floor | EI 180 - u/c |
Pyroplex Limited have a Quality Management System that meets the requirements of ISO 9001 and an Environmental Management System that meets the requirements of ISO 14001, both are independently verified by BSI Quality Assurance under Certificate Numbers FM 10371 and EMS 637894.
Copies of these certificates are available on our website to download in the "Data Sheets" tab further above.
Product Testing
Pyroplex Limited have carried out numerous independent fire resistance tests to confirm the suitability of the product and to demonstrate product compliance by utilising BS EN 1366-3. EN classification reports to BS EN 13501-2 is available for download from our "data Sheets" tab further above.
Pyroplex 200 series wraps refer to EN Classification reports WF174256/C Issue 2 and 387452 Issue 1. Pyroplex 400 series wraps refer to EN Classification reports WF174256/D Issue 1.
Structural Constructions
Pyroplex CE Marked Pipe Wraps can be used in walls and floors, with a solid construction of a density not less than 650kg/m3. Pyroplex CE Marked Pipe Wraps must not be used in stud wall partitioning systems.
The wall or floor shall not be less than 100mm in overall thickness. It is recommended that the overall distance between the wrap and the hole does not exceed 5mm. Failure to observe this may result in underperformance in a fire situation.
Specification of Wraps
The Pipe Wrap consists of a polyethylene sleeve which contains a single or multiple layers of intumescent material. For pipe diameters of 125mm-160mm (4 hour wraps only) the intumescent is contained within a glass-fibre woven sock. The sleeve is provided with a self-adhesive tag to aid installation.
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.