Pyroplex Putty Pads For Electrical Boxes

    NOR5005
    NOR5005

    Pyroplex Putty Pads, pre-cut ablative pads designed to reinstate the fire performance of compartment walls when penetrated by electrical outlets, providing a fast, efficient and clean method of achieving the required fire performance.

    • Tested in accordance with BS EN 1364-1
    • Can be used in masonry and plasterboard partitions up to 120 minutes fire performance
    • Can be used in conjunction with Metallic and Thermoplastic electrical switch boxes
    • Suitable for use in single and double outlets
    • No mechanical fixings required
    • Coloured light red to distinguish its fire capabilities

    Colour
    Item
    £4.68(ex. VAT)
    £5.62 (inc. VAT)
    Quantity
    Please choose your colour
    Available for Delivery (See Delivery Options Below)

    Description

    Pyroplex Putty Pads are pre-cut ablative pads which have been specifically designed to reinstate the fire performance of compartment walls when penetrated by electrical sockets, thereby reducing the need for additional backing materials. Putty Pads provide a fast, efficient and clean method of achieving the required fire and acoustic ratings as required by Building Regulations Approved Documents.

    The product is a non-halogenated silicone based compound with additional fillers and extenders to produce mouldable and non-setting component. The product can be moulded and used internally and externally around the electrical box.

    The product has been tested in accordance with BS EN 1364-1, achieving up to 120 minutes fire resistance.



    Quick Links - Click To Jump To Section:




    Features & Benefits


    • Pre-cut ablative pads designed to reinstate the fire performance of the compartment wall when penetrated by electrical outlets
    • They provide fast, efficient and clean method of achieving the required fire performance
    • Can be used in masonry and plasterboard partitions up to 120minutes fire performance
    • Can be used in conjunction with Metallic and Thermoplastic electrical switch boxes
    • Suitable for use in single and double outlets
    • No mechanical fixings required
    • Coloured light red to distinguish its fire capabilities



    Ordering References


    ReferenceSize (mm) nominal dimensionsEnd use application
    PUTPAD170170mm x 170mm x 3.25mmSingle outlet
    PUTPAD230230mm x 170mm x 3.25mmDouble outlet

    Note: Components individually wrapped in a filmic liner



    Installation Instructions


    Internal

    To achieve a high quality seal, ensure the socket is clean and free from any dirt, dust and that it is dry.

    • Remove the protective film liner from putty pad.
    • Make a slit in the pad which will enable the cable to be passed through.
    • Press the pad firmly into the socket recess ensuring full contact is made to all sides.
    • Make sure the pad is not damaged or punctured during this process.
    • Remove the remaining film liners and trim off any excess material to leave a neat finish.

     

    External

    To achieve a high quality seal, ensure the socket is clean and free from any dirt, dust and that it is dry.

    • Remove the protective film liner from putty pad.
    • Mould the component around the extremities of the box to make an effective seal, trimming an excess of material.



    Quality Approval


    Meets the requirements of ISO 9001, and is independently verified by BSI Quality Assurance under Certificate No. FM10371. Copies of this approval are available on request - contact our technical team on 0113 2455450 (option 2) or send a message to [email protected] for more information.



    Testing


    The product has been tested in accordance with BS EN 1364-1 and the general requirements of BS EN1363-1, achieving up to 120minutes fire resistance. Test report is available upon request.



    Structural Constructions


    Rigid floors:

    The floor must have a minimum thickness of 150mm and comprise of aerated concrete or concrete with a minimum density of 650 kg/m3.

     

    Flexible Walls:

    The wall must have a minimum thickness of 130mm and comprise either or timber or steel studs lined on both faces with a minimum 2 layers of 15mm Type F Gypsum boards according to EN520.

    In timber stud walls, no part of the penetration shall be closer than 100mm to a stud, and minimum of 100mm of insulation compliant with Class A1 or A2 according to EN13501-1, be provided within the cavity between the penetration and the stud.

    Flexible Wall Constructions - 2 layers of 15mm FR Plasterboard Partition 70mm Steel C Stud (unexposed and unexposed) Single and Doubled Electrical Outlets
    SubstrateOutlet TypePosition of protectionFire resistance
    Gypsum boardDouble (230mm x 170mm)Putty pad externally mounted and internally mounted to the electrical socket outletEI 120

     

    IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.

    Product Details
    5005-803700

    Data sheet

    Manufacturer
    Norseal
    Key Features
    Up to 120 minutes fire performance
    Product Usage Type
    Sealer
    Product Range
    Pyroplex
    Colour Family
    Red
    Fire Rating
    120 Minutes
    Attachments
    Download


    Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.


    Be the first to ask a question about this product!


    Question about the product

    * Required fields
    (read)
    Send

    IMPORTANT SHIPPING & DELIVERY INFORMATION

    Pyroplex Putty Pads For Electrical Boxes is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.

    Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.

    Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.

    All delivery costs below are excluding VAT