Norseal Pyroplex Fire Rated Silicone Sealant, a one part, low modulus, neutral cure, halogen free product suitable for the sealing of construction joints, and around pipe penetrations which have been protected by the recommended Pyroplex intumescent product.
Norseal Pyroplex Fire Rated Silicone Sealant is a one part, low modulus, neutral cure, halogen free product suitable for the sealing of construction joints, and around pipe penetrations which have been protected by the recommended Pyroplex Pipe Collar and Pipe Wrap. Also ideal for the weathersealing of curtain walling, building facades and expansion joints in fire rated walls.
Fire rated up to 240 minutes, Norseal Pyroplex Fire Rated Silicone Sealant offers excellent adhesion to many common building substrates and has outstanding resistance to ozone, UV and temperature extremes, tack-free within two hours.
Tested to BS EN 1366-4 and has a European Classification EI 240 in accordance with BS EN 13501-2.
Designed for use when:
Ref. | Seal width | Seal depth | Joint type | Backing media | Integrity | Insulation |
---|---|---|---|---|---|---|
E | 15mm | 10mm | Single | PE | 240 mins | 180 mins |
F | 40mm | 25mm | Double | MW | 240 mins | 240 mins |
J | 25mm | 15mm | Single | PE | 240 mins | 120 mins |
L | 15mm | 10mm | Double | MW | 240 mins | 240 mins |
Pyroplex Limited have a Quality Management System that meets the requirements of ISO 9001 and an Environmental Management System that meets the requirements of ISO 14001, both are independently verified by BSI Quality Assurance under Certificate Numbers FM 10371 and EMS 637894. Copies of these certificates are available, contact our technical team for more information on 0113 2455450 (option 2) or send a message to [email protected].
Product Testing
A number of independent fire resistance tests have been carried out to confirm the suitability of the product and to demonstrate product compliance by utilising BS EN 1366-4 and other international standards. Pyroplex® Fire Rated Silicone Sealant has a European Classification EI240 in accordance with BS EN 13501-2.
Joint Configuration
The fire resistance performance of the material is based upon the joint configuration and the position and location of the seal, within the construction and backing materials used.
Backing Material
Backing materials | |
---|---|
PE | Polyethylene, with a nominal density of 0.35kg/m3 |
MW | Mineral wool, with a nominal density of 100kg/m3 |
Structural Construction
Pyroplex Fire Rated Silicone Sealant can be used in walls and floors of a solid construction.
Construction element | Fire resistance period [mm] | Minimum thickness | Material types and minimum density |
---|---|---|---|
Wall and floor | Up to 120 minutes | 100mm | Solid masonry work*, with a density no less than 650kg/m3 |
Wall and floor | Up to 240 minutes | 150mm> | Solid masonry work*, with a density no less than 650kg/m3 |
* Aerated concrete, lightweight ash blocks and/or solid brick construction.
Wall construction and fire resistance periods: Aerated concrete, lightweight ash blocks and/or solid brick construction.
Consumption Guide
Depth | Width | ||||
---|---|---|---|---|---|
6mm | 10mm | 15mm | 20mm | 25mm | |
10mm | 5m | 3m | 2m | 1m | 1m |
15mm | 3m | 2m | 1m | 1m | 0.8m |
20mm | 2m | 1m | 1m | 0.7m | 0.6m |
Linear metres per 310ml cartridge, the figures quoted estimated and for guidance only.
Maintenance and Installation Records
Pyroplex Limited recommend that all firestopping materials are checked on a regular basis to ensure that the product remains integral.
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.