Pyrocoustic Fire Resistant Sealant is a water-based acrylic sealant used to reinstate the fire resistance of wall and floor constructions in linear joints and where apertures are penetrated by multiple services. Developed utilizing specialist polymer technologies allowing it to be tested and Certified to internationally recognised standards, including Certifire, CE marking and UL Listings.
Choose between cartridges, foils, and trowel-grade pails
Mechanical Adhesion, Tensile testing & Shore Hardness to ISO 9046:2005, ISO 8339:2005 & ISO 7619-1:2011
Fire resistance tested in flexible walls, rigid walls and floors
Tested in Linear Joints up to 50mm wide
Tested in large service openings up to 490 x 150mm
Tested with Metallic Pipes, Cables, Cable Bunches, Cable Trays and Cable Ladders
Causes no known effects to plastic pipes, plastic cables, sheathing or metallic components
Pyrocoustic Fire Resistant Sealant is a water-based acrylic sealant used to reinstate the fire resistance of wall and floor constructions in linear joints and where apertures are penetrated by multiple services. Pyrocoustic Fire Resistant Sealant has been developed utilizing specialist polymer technologies allowing it to be tested and Certified to internationally recognised standards, including Certifire, CE marking and UL Listings.
Pyrocoustic Fire Resistant has been tested and Certified as part the FSi Fire Stopping range. The Pyrocoustic system can be installed across a variety services and substrates including:
Flexible and Rigid Walls
Rigid Floors
Multi-Service penetrations
Blank Openings
Head of Walls
Stopseal Ablative Batt
Ref
Item
Quantity
FS310CW25
Pyrocoustic Fire Resistant Sealant 310ml Cartridge - White
Box of 25
FS310CG
Pyrocoustic Fire Resistant Sealant 310ml Cartridge - Grey
Box of 25
FS310CB
Pyrocoustic Fire Resistant Sealant 310ml Cartridge - Brown
Box of 25
FS400CW
Pyrocoustic Fire Resistant Sealant 400ml Foil - White
Box of 21
FS600CW
Pyrocoustic Fire Resistant Sealant 600ml Foil - White
Box of 15
FS600CG
Pyrocoustic Fire Resistant Sealant 600ml Foil - Grey
Box of 15
FS900CW
Pyrocoustic Fire Resistant Sealant 900ml Cartridge - White
Mechanical Adhesion, Tensile testing & Shore Hardness to ISO 9046:2005, ISO 8339:2005 & ISO 7619-1:2011
Fire resistance tested in flexible walls, rigid walls and floors
Tested in Linear Joints up to 50mm wide
Tested in large service openings up to 490 x 150mm
Tested with Metallic Pipes, Cables, Cable Bunches, Cable Trays and Cable Ladders
Causes no known effects to plastic pipes, plastic cables, sheathing or metallic components
For use in low movement joints, remains flexible
Halogen free, resists fungi and vermin
Certifire 3rd Party Certification CF 517
Water-based acrylic sealant
Used to reinstate the fire resistance of wall and floor constructions in linear joints and where apertures are penetrated by multiple services
Tested and Certified to internationally recognised standards, including Certifire, CE marking and UL Listings
Can be installed across a variety services and substrates
Prevention of air leakage
Maintains Acoustic performance
Assumed working life 30 years
Flexible, high performance water based Fire Resistant Sealant, for use in gaps up to 60mm
Tested within the Stopseal Batt System
Conditioned to Type X in accordance with EOTA TR024
Tested in accordance with many major global certification standards
Easy gunning and tooling
Tested practically, with the installer in mind. Tested with various common backing materials
Provides smoke seal
Manufactured and tested alongside the entire FSi Fire Stopping range in the UK
Areas of Use
To reinstate fire resistance through walls and floors
Linear Construction Joints
Prevention of air leakage
Maintains Acoustic performance
Assumed working life 30 years
Certification & Testing
Tested in accordance with EN1366-3:2009 – Fire Resistance – Penetration Seals
Tested in accordance with EN1366-4:2009 – Fire Resistance – Linear Seals
Classified in accordance with EN13501-2 – Fire Resistance
CE Marked – ETA 13-1069 & ETA 13-1070
Tested in accordance with ASTM E2923:14 – Longevity of Fire Stop Materials
Conditioned in accordance with EOTA TR024 – X Type
Certifire Accreditation – CF517
ULEU Accreditation
ULUS Listing
UAE Certificate of Compliance
Tested in accordance with EN10140-2:2010 – Airborne Sound
Tested in accordance with EN1026:2000 - Air Permeability
General Characteristics
General Characteristics
Inspection Method
Value
Product Data (uncured)
Density (S.G)
ASTM D792:13
1.63
Appearance
Paste, matt finish
Resistance to flow
ISO 7390 : 2003
Pass
Product Data (after curing)
Hardness Shore A
ISO 7619-1 : 2010
63/39
Movement Capability
7.50%
Operating Temperature °C
-5 to 40
Loss Mass of Mass on Heating
ISO 3451-1 (Method A)
68.34
Flexibility - Bend Test
ISO 1519
Pass
Longevity of Firestop Materials
ASTM E2923 : 14
30 Years
Conditioning
EOTA TR024
Type X
Product Technical Data
Description
Result
Test Standards
Slump
5mm aGer 1hr in 30mm joints
Shrinkage
Approximately 12%
Cure Rate
3mm per day at 50% relative humidity 23°C
Specific Gravity
1.56 - 1.66 g/cm3
ISO 2811-1:2011
Application temperature
5°C to 40°C
Tack Free
30 mins at 23°C, 50% RH
Water Resistance
Good when fully cured
U.V. Resistance
Good
Joint Movement
Remains flexible
EN 1366-4:2006 + A1:2010
VOC % Nonaqueous volatiles (105°C)
3.6
LEED
Acoustic
Up to Rw(C;Ctr) :63(-2;-7) dB
EN ISO 10140-2:2010
BREEAM International
Compliant
GN22: BREEAM Recognised Schemes for VOC Emissions from Building Products
Expected Shelf Life
18 Months unopened
Stored in accordance with packaging instructions
Backing Material
Mineral wool (min. 80kg/m3) or PE backing rod where required can be use as backing materials, though the Pyrocoustic Sealant should be installed correctly to achieve the performance needed.
Key Installation Points
Pyrocoustic Sealant to be used installing FSi Stopseal Batts.
For good adhesion the surfaces of the building elements shall be free of any dust or grease and may need to be primed on good clean, virgin concrete & masonry, no priming required.
Ensure that the aperture and services in question are tested with Pyrocoustic Sealant and the site conditions are within the application specification. An annular space needs to be present around the service to apply sufficient installation depth.
All services and apertures need to be clean and clear of all dust and loose particles. The aperture temperature needs to at 5℃ or above at time of installation.
Upon installation make sure that you install the Pyrocoustic Sealant around all services needed.
Once compacted, smooth off the Pyrocoustic Sealant to produce a professional finish.
Performance Data
Please refer to the Technical Data Sheet in the "Data Sheets" tab further above for information on the below areas:
Linear Joint Seals - Walls (page 3 - 5)
250mm Rigid Walls
100mm Rigid Walls
120mm Rigid Walls
Linear Joint Seals - Floors (page 6 - 7)
150mm Rigid Floors
Movement (page 8)
150mm Rigid Walls
150mm Rigid Floors
Penetration Seals (page 9 - 11)
150mm Flexible and Rigid Walls
100mm Flexible and Rigid Walls
75mm Flexible and Rigid Walls
Extended Scope of Works (page 12)
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contactedto obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditionsand should be applied only by an individual with the necessary expertise and experience.We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.
FSi Pyrocoustic Fire Resistant Sealant is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
An ablative-coated stonewool board used to reinstate the fire resistance performance of internal wall and floor constructions where apertures are penetrated by single or multiple services.Prevention of air leakage and provides smoke seal Maintains Acoustic performance Assumed working life 30 years Highly flexible, high performance...