FSi Flexi Coat Flexible Ablative Coating, a highly advanced flexible penetration and aperture sealing system, supplied in the form of both completed pre-coated Flexi-Coat Fingers and as a coating to be applied to stone/mineral wool backing material. Tested in accordance with EN1364-4 and is third party certified.
FSi Flexi Coat Flexible Ablative Coating is a highly advanced flexible penetration and aperture sealing system, supplied in the form of both completed pre-coated Flexi-Coat Fingers and as a coating to be applied to stone/mineral wool backing material. Tested in accordance with EN1364-4 and is third party certified.
Intended areas of use
Product Description | |
---|---|
Colour | White (others on request) |
Cure Rate | 0.5mm per day at 50% relative humidity @ 23℃ |
Tack Free | 6hrs at 23℃, 50% RH |
Coating Thickness | 2.5mm nominal, wet coating thickness |
Coverage | 2.8kg/m2, 2.24L/m2 |
Classification | EN 13501-2, EN 13501-1 |
Movement | +/- 25% |
Shelf Life | 18 months for wet product |
Test Description | Result | Test Standard |
---|---|---|
Specific Gravity (coating) | 1.2 - 1.35g/cm3 | ISO 2811-1:2011 |
Fire Resistance | Up to EI 120 | EN 13501-2, EN 1366-3, EN 1366-4, EN1364-4 |
Reaction to fire | B-s1, d0 | EN 13501-1 |
Acoustic | Up to 49dB | EN ISO 10140-2:2010 |
Air Permeability | 600 Pa EN 1026 - 100Pa 0.4/1.5 m3/h/m2 | EN1026 |
Water Permeability | 450 Pa - No Leakage | EN 1027 |
VOC % Non-aqueous volatiles (105℃) | 11 | LEED |
Substrates
Please refer to the Product Data Sheet in the "Data Sheets" tab further above for information on the below areas:
Walls shall be a minimum of 100mm thick. Substrates shall be classified in accordance with EN13501-2 to the required fire resistance period. Masonry / Concrete walls shall have a minimum density for concrete or brick of 780kg/m3 and for aerated concrete blocks of 600kg/m3. All substrates shall have at least the same fire resistance as that required for the sealing system.
Service Support Requirements
Services should be rigidly supported via steel angles, hangers or channels, not further than 250mm from the surface of the sealing system on both faces of wall and top face of floor unless specified otherwise in the performance data.
Classification Terminology
Fire resistance classes are:
Pre-Installation
Ensure that the aperture and services in question are tested with Flexi-Coat system, and the site conditions are within the application specification. For combustible services when PyroPro HPE is used, a sufficient annular space needs to be present around the service to apply sufficient installation depth. All services and apertures need to be clean and clear of all dust and loose particles. The aperture temperature needs to at 5℃ or above at time of installation. The Flexi-Coat system must be in the orientation that ensure the lamellas are positioned to allow for compression. For Flexi-Coat installation, stone wool backing material must be manufactured in accordance with EN 13162: 2001.
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions and should be applied only by an individual with the necessary expertise and experience. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.
FSi Flexi Coat Flexible Ablative Coating is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
All delivery costs below are excluding VAT