PPG SteelGuard 564

7768

PPG SteelGuard 564 is a one-component, thin-film, solvent-borne intumescent coating for fire protection of structural steelwork. Steelguard 564 is fast-drying and can provide up to 120 minutes protection.

  • Suitable for C1 to C4 internal and external environments (ISO 12944); for dry internal (C1) environments no topcoat is required
  • Tested and assessed to international and national standards such as BS 476-20/21 and Factory Mutual Class number 4970 and certified with various national requirements
  • Used at Résidence Palace, Brussels, Belgium
Colour
Size
Finish
£557.20
VAT excluded

£668.64 Tax incl.
Quantity

Description

PPG SteelGuard 564 is a one-component, thin-film, solvent-borne intumescent coating for fire protection of structural steelwork. Steelguard 564 is fast-drying and provides up to 120 minutes protection from cellulosic fires.



Top Features & Benefits


  • Off-site or on-site application
  • Up to 1000 µm (40.0 mils) DFT in a single coat
  • Suitable for C1 to C4 internal and external environments (ISO 12944); for dry internal (C1) environments no topcoat is required
  • Weather resistant up to 12 months without topcoat provided the coating has been applied in accordance with INFORMATION SHEET 1222 and is not subject to running or pooling water, high humidity or immersion conditions
  • Tested and assessed to international and national standards such as BS 476-20/21 and Factory Mutual Class number 4970 and certified with various national requirements
  • Matt Finish
  • Used at Résidence Palace, Brussels, Belgium



Product Data


Basic data at 20°C (68°F)

Data for Product
Number of components One
Mass density 1.34 kg/l (11.18 lb/US gal)
Volume solids 75 ± 3%
VOC (Supplied) Directive 1999/13/EC, SED: max. 255.0 g/kg UK PG 6/23(92) Appendix 3: max. 327.0 g/l (approx. 2.7 lb/US gal) EUR Directive: 2004/42/IIA(i)(500) 367 g/l)
Recommended film thickness 200 - 1000 µm (8.0 - 40.0 mils) per coat
Theoretical spreading rate 1.07 m²/l for 700 µm (43 ft²/US gal for 28.0 mils)
Dry to touch 20 minutes
Overcoating interval Minimum: 4 hours
Maximum: Unlimited
Shelf life At least 18 months when stored cool and dry

Notes:
See ADDITIONAL DATA – Spreading rate and film thickness
See ADDITIONAL DATA – Overcoating intervals
See ADDITIONAL DATA – Curing time
The required dry film thickness must be in accordance with the approval certification.

Recommended Substrate Conditions and Temperatures

  • Approved primer must be sound, dry and free from any contamination Substrate temperature and application conditions
  • Substrate temperature during application and curing should be between 5°C (41°F) and 40°C (104°F)
  • Substrate temperature during application and curing should be at least 3°C (5°F) above dew point
  • Ambient temperature during application and curing should be between 5°C (41°F) and 40°C (104°F)
  • Relative humidity during application and curing should not exceed 85%

Instructions for Use

  • Stir thoroughly until homogeneous and free of lumps
  • Adding too much thinner results in reduced sag resistance and slower cure

Airless spray
Recommended thinner: THINNER 21-06 (normally no thinner required)
Volume of thinner: 0 - 5%
Nozzle angle: 20° – 50°, depending on shape of steel parts
Nozzle orifice: Approx. 0.48 – 0.64 mm (0.019 – 0.025 in)
Nozzle pressure: 20.0 MPa (approx. 200 bar; 2901 p.s.i.)

Notes:
All filters, including surge bottle and gun filters to be removed. External fluid uptake pipe filter is recommended

Brush/roller
For small areas only (touch up and repair). No thinner should be added.

Cleaning Solvent
THINNER 21-06



Overcoating interval for DFT up to 700 µm (28 mils)
Overcoating with... Interval 5°C (41°F) 10°C (50°F) 15°C (59°F) 20°C (68°F) 30°C (86°F)
Itself Minimum
Maximum
10 hours
Unlimited
8 hours
Unlimited
6 hours
Unlimited
4 hours
Unlimited
3 hours
Unlimited



Overcoating interval for DFT up to 1000 µm (40 mils)
Overcoating with... Interval 5°C (41°F) 10°C (50°F) 15°C (59°F) 20°C (68°F) 30°C (86°F)
Steelguard 2458 Minimum
Maximum
2 hours
Unlimited
1.5 hours
Unlimited
1 hour
Unlimited
30 minutes
Unlimited
20 minutes
Unlimited
Other approved coats Minimum
Maximum
3 days
Unlimited
60 hours
Unlimited
48 hours
Unlimited
24 hours
Unlimited
16 hours
Unlimited



Curing time for DFT up to 25 µm (1.0 mils)
Substrate Temp. Dry to Touch
5°C (41°F) 1 hour
10°C (50°F) 45 minutes
15°C (59°F) 30 minutes
20°C (68°F) 20 minutes
30°C (86°F) 10 minutes

Note: Drying times may vary considerably depending on ambient conditions, A/V m⁻¹ (Hp/A) of section and applied film thickness.



References

  • STEELGUARD™ APPLICATION GUIDELINES - INFORMATION SHEET 1222
  • STEELGUARD™ QUALIFIED PRIMERS - INFORMATION SHEET 1224
  • STEELGUARD™ QUALIFIED TOPCOATS - INFORMATION SHEET 1226
  • CONVERSION TABLES - INFORMATION SHEET 1410
  • EXPLANATION TO PRODUCT DATA SHEETS - INFORMATION SHEET 1411
  • SAFETY INDICATIONS - INFORMATION SHEET 1430
  • SAFETY IN CONFINED SPACES AND HEALTH SAFETY, EXPLOSION HAZARD AND TOXIC HAZARD - INFORMATION SHEET 1431
  • CLEANING OF STEEL AND REMOVAL OF RUST - INFORMATION SHEET 1490
  • SPECIFICATION FOR MINERAL ABRASIVES - INFORMATION SHEET 1491
  • RELATIVE HUMIDITY – SUBSTRATE TEMPERATURE – AIR TEMPERATURE - INFORMATION SHEET 1650

It is your responsibility to read the Product Data Sheets (available below) before you place an order and prior to application of the product. The content of this website is our best recommendation and is not advice. Coverage rates quoted are approximate, you agree that coverage depends on the condition of the substrate, surface absorption, texture and application method. We ALWAYS recommend a trial area is coated to ensure the product meets your requirements before use.

Product Details
7768

Data sheet

Manufacturer
PPG
Parts
One
Base Type
-
Solvent
Solvent-based
Mixing Ratio
-
Suitable Substrates
Structural steel
Key Features
provides up to 120 minutes protection from cellulosic fires, off-site or on-site application, suitable for C1 to C4 internal and external environments (ISO 12944); for dry internal (C1) environments no topcoat is required
Application
Spray
Touch Dry (at 20°C)
20 minutes
Dry to Handle (at 20°C)
-
Dry to Recoat (at 20°C)
4 hours
Fully Cured (at 20°C)
-
Pot Life (at 20°C)
-
Coverage
1.07 m²/l for 700 µm (43 ft²/US gal for 28.0 mils)
Recommended Thinner/Cleaner
PPG Thinner 21-06
Unit Contents
-
Compatible Primers
-
Compatible Topcoats
Itself, PPG Steelguard 2458
Max. Application Temperature
40°C (104°F)
Min. Application Temperature
5°C (41°F)
Density
1.34 kg/l (11.18 lb/US gal)
Solids by Volume
75 ± 3%
Heat Resistance (up-to)
-
VOC
Directive 1999/13/EC, SED: max. 255.0 g/kg UK PG 6/23(92) Appendix 3: max. 327.0 g/l (approx. 2.7 lb/US gal) EUR Directive: 2004/42/IIA(i)(500) 367 g/l)
Shelf Life (Once Opened)
At least 18 months when stored cool and dry
UN Number
UN1263
Attachments
Download


Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.


Be the first to ask a question about this product!


Question about the product

* Required fields
(read)
Send
You might also like

PPG Thinner 21-06

This thinner has been developed by PPG Protective and Marine Coatings for use with selected paint products.

Price £19.43
In stock