Tenmat FF109 Pipe Fire Sleeves

PFS017

Tenmat FF109 Pipe Sleeves are particularly suitable for use in plasterboard partitions, but can be used in blockwork walls and floors, and typically provide 2 hours, and in certain applications up to 4 hours, fire resistance to various plastic and metal pipes. The Sleeves do not require any additional metal sleeving and the unique intumescent material is vacuum formed to shape which ensures controlled sealing of the plastic pipe.

  • Up to EI120 Minutes Fire Rated in Partitions
  • Up to EI240 Minutes Fire Rated in Blockwork
  • Acoustic, Thermal and Vapour seal
  • Fire tested to EN 1366-3:2009 & BS 476
  • European Technical Approval (ETA-12/0332)
  • EC Certificate 1224-CPR-0341
  • Note: some sizes are currently only available on a 2-3 week delivery service - please see below for more information

**Available for delivery - see Delivery Options below**

Colour
Item
£20.52
VAT excluded

£24.62 Tax incl.
Quantity

Description
Ref Item Availability
PFS017 TENMAT FF109 Pipe Sleeve 17mm In Stock
PFS021 TENMAT FF109 Pipe Sleeve 21mm In Stock
PFS027 TENMAT FF109 Pipe Sleeve 27mm 2-3 weeks
PFS034 TENMAT FF109 Pipe Sleeve 34mm In Stock
PFS042 TENMAT FF109 Pipe Sleeve 42mm 2-3 weeks
PFS048 TENMAT FF109 Pipe Sleeve 48mm In Stock
PFS054 TENMAT FF109 Pipe Sleeve 54mm In Stock
PFS060 TENMAT FF109 Pipe Sleeve 60mm 2-3 weeks
PFS067 TENMAT FF109 Pipe Sleeve 67mm 2-3 weeks
PFS076 TENMAT FF109 Pipe Sleeve 76mm In Stock
PFS080 TENMAT FF109 Pipe Sleeve 80mm 2-3 weeks
PFS089 TENMAT FF109 Pipe Sleeve 89mm 2-3 weeks
PFS102 TENMAT FF109 Pipe Sleeve 102 mm In Stock
PFS108 TENMAT FF109 Pipe Sleeve 108 mm 2-3 weeks
PFS114 TENMAT FF109 Pipe Sleeve 114 mm 2-3 weeks
PFS127 TENMAT FF109 Pipe Sleeve 127 mm 2-3 weeks
PFS140 TENMAT FF109 Pipe Sleeve 140mm 2-3 weeks
PFS159 TENMAT FF109 Pipe Sleeve 159mm 2-3 weeks
PFS169 TENMAT FF109 Pipe Sleeve 169mm 2-3 weeks

Tenmat FF109 Pipe Sleeves are particularly suitable for use in plasterboard partitions, but can be used in blockwork walls and floors, and typically provide 2 hours, and in certain applications up to 4 hours, fire resistance to various plastic and metal pipes. The Sleeves do not require any additional metal sleeving and the unique intumescent material is vacuum formed to shape which ensures controlled sealing of the plastic pipe.

  • Up to EI120 Minutes Fire Rated in Partitions
  • Up to EI240 Minutes Fire Rated in Blockwork
  • Acoustic, Thermal and Vapour seal
  • Fire tested to EN 1366-3:2009 & BS 476
  • European Technical Approval (ETA-12/0332)
  • EC Certificate 1224-CPR-0341
  • Click to jump down to Technical Data

Tenmat FF109 Pipe Sleeves typically provide 2 Hours, and in certain applications up to 4 Hours Fire Resistance to various plastic and metal pipes.

The Fire Sleeves have been fire tested to EN 1366-3:2009 & BS 476. The European Technical Approval (ETA-12/0332) and EC Certificate 1224-CPR-0341 enables the range to be CE Marked and used throughout the EU.

Tenmat FF109 Pipe Sleeves are particularly suitable for use in plasterboard partitions, but can be used in blockwork walls and floors.

The Sleeves do not require any additional metal sleeving. The unique intumescent material is vacuum formed to shape which ensures controlled sealing of the plastic pipe.



Quick Links - Click To Jump To Section:




Features & Benefits


  • CE Marked Pipe Fire Sleeves providing fire resistance to various plastic and metal pipes
  • Up to EI120 Minutes Fire Rated in Partitions
  • Up to EI240 Minutes Fire Rated in Blockwork
  • Particularly suitable for use in plasterboard partitions, but can be used in blockwork walls and floors CE Marked
  • Acoustic, Thermal and Vapour seal
  • Fire tested to EN 1366-3:2009 & BS 476
  • European Technical Approval (ETA-12/0332)
  • EC Certificate 1224-CPR-0341



Product Dimensions


Ref Diameter Length
PFS017 17mm 300mm
PFS021 21mm 300mm
PFS027 27mm 300mm
PFS034 34mm 300mm
PFS042 42mm 300mm
PFS048 48mm 300mm
PFS054 54mm 300mm
PFS060 60mm 300mm
PFS067 67mm 300mm
PFS076 76mm 300mm
PFS080 80mm 300mm
PFS089 89mm 300mm
PFS102 102 mm 300mm
PFS108 108 mm 300mm
PFS114 114 mm 300mm
PFS127 127 mm 300mm
PFS140 140mm 300mm
PFS159 159mm 300mm
PFS169 169mm 300mm

 

  • Sleeves are supplied 300mm long as standard
  • Shorter lengths may be available on request
  • Nominal wall thickness—30mm



Approvals


Independently Third Party Assessed:

30 Minute Partitions

  • Single Board from 72mm upwards

 

60 Minute Partitions

  • Single & Double Board Systems
  • Single Layer Ablative Coated Fire Batt

 

120 Minute Partitions

  • Double Board Systems
  • Double Layer Ablative Coated Fire Batt

 

CE Mark Approved:

3rd Party Assessed and Audited

 

BS 476 and BS EN 1366-3 Fire Tested

 

Fire Tested & Assessed for Blockwork

Up to 4 Hour Tested



Example Approved Applications


TENMAT’s Pipe Fire Sleeve is approved for a wide range of applications, outlined on page 9 of the Fire Stopping Brochure. All details for approved applications can be seen in the ETA, fire test and assessment reports which are available to download from thedata sheets tab further above.

 

Wall Penetrations:

  • Plasterboard (Approved with or without cavity insulation)
  • Concrete/Masonry Wall
  • Ablative Coated Fire Batt

 

Floor Penetrations:

  • Concrete floor
  • Concrete floor with Firestop Compound



General Fitting Instructions


For detailed fitting instructions for various applications please contact our technical support team on 0113 2455450 (option 2) or send a message to [email protected].

  • Use the Fire Sleeve as a template when cutting the partition to provide a snug fit around the Fire Sleeve
  • Cut sleeve to length if required
  • Make a slit along sleeve length to allow fitting around pre-installed pipes

  • Fit sleeve around pipe
  • Slit should be resealed with Aluminium Foil Repair Tape provided
  • Slide Fire Sleeve until required minimum protrusion either side of partition is obtained (see below)

  • The Fire Sleeve must protrude each side of the partition by 25mm minimum for combustible pipes
  • Plasterboard should be a snug fit, however any gaps (up to 5 mm) should be sealed with intumescent sealant



Examples of Projects


Commercial/Residential

  • The Leadenhall Building (Cheesegrater)
  • London Olympic Village
  • One Tower Bridge

 

Medical/Healthcare

  • Royal Stoke University Hospital
  • Salford Royal Hospital



Test Data


Report Type Fire Test Lab RepolNumter Construction Fire Rating
Certificate Exova BM Trada 1224-CPR-0341 Various CE Marked
European Technical Approval Exova BM Trada ETA 12/0332 Various Up to 240
Classification Exova Warringtonfire CR12001 A Plasterboard 30-120
Classification Exova Warringtonfire CR12001 B Plasterboard/Concrète 90-240
Classification Exova Warringtonfire CR12001 C Plasterboard/Concrète 120-240
Assessment Exova Warringtonfire 33654700.2 Plasterboard, Concrète, Floor 60-120
Assessment IFC Group PAR/13814/02 Ablative Coated Fire Batt 120
Fire Test Exova Warringtonfire A03187 Various 10-120
Fire Test Exova Warringtonfire RF11067 Plasterboard 30-120
Fire Test Exova Warringtonfire IF11082 Concrete 120
Fire Test Exova Warringtonfire IF11059A Concrete 90-120
Fire Test Exova Warringtonfire IF11049 Concrete 120
Fire Test Exova Warringtonfire IF09045 Concrete 240
Fire Test Exova Warringtonfire IF04040a Blockwork Floor 120
Fire Test Exova Warringtonfire IF03030 Plasterboard 120
Fire Test Exova Warringtonfire IF02087A Masonry Floor 120
Fire Test Exova Warringtonfire IF02087B Plasterboard 120
Fire Test Exova Warringtonfire IF02045 AR1 Ablative Coated Fire Batt 60-120
Acoustic Test BRE 239037 Plasterboard Pass
Thermal Test BBA BC 0474 N/A 0.035 W/(m K)

 

IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contacted to obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditions. We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.

Product Details
PFS017

Data sheet

Key Features
Typically up to 2 hours, some instances up to 4 hours
Attachments
Download


Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.


Be the first to ask a question about this product!


Question about the product

* Required fields
(read)