Sherwin-Williams Firetex FX2007 is a single pack thin film intumescent coating designed for in-shop application by airless spray, to provide fire resistance for up to 60 minutes on structural steel.
Endorsements include:
Tested and assessed to EN13381-8 and BS EN13381-9
CE Mark Number: 2812-CPR-GA5055
European Technical Assessment: ETA-22/0352
Certifire Approved - Certificate CF6088
Can resist normal weather conditions for up to 6 months without topcoat provided it has had appropriate drying prior to exposure
For certain dry, internal situations where the final colour/ appearance is not critical, then Firetex FX2007 may remain un-topcoated
Please note that this product should not be used without first receiving an application schedule from our Technical Department. Please download and complete the 'FIRETEX Intumescent Support Request Form' and return by email to [email protected]
If you have any questions regarding this process consult our technical department on 0113 2455450 (option 2).
Provides fire resistance for up to 60 minutes on structural steel
After appropriate drying, Firetex FX2007 specifications can be exposed to the weather for up to 6 months provided that the specific use or storage does not lead to ponding water due to rainfall, condensation or other site circumstances
Tested and assessed to EN13381-8 and BS EN13381-9
CE Mark Number: 2812-CPR-GA5055
European Technical Assessment: ETA-22/0352
Certifire Approved - Certificate CF6088
Recommended application methods
Airless Spray
Can resist normal weather conditions for up to 6 months without topcoat provided it has had appropriate drying prior to exposure. After this time period an appropriate top coat shall be applied
If the specific use or storage could lead to prolonged contact with water due to rainfall, condensation, or other site / transportation / storage circumstances, then a recommended topcoat must be used to prevent damage to the basecoat
Touch dry in approx. 20 minutes at 23°C, re-coat in approx. 4 hours at 23°C
Recommended Primers/Topcoats
Several primers have been approved for use under Firetex FX2007. For certain dry, internal situations where the final colour/ appearance is not critical, then Firetex FX2007 may remain un-topcoated
For externally exposed steelwork and severe internal environments Acrolon A7300, Acrolon C137V2 or Acrolon C237 must be used as a topcoat
For other internal environments where a topcoat is required then Firetex M71V2 or Sher-Cryl M770 should be used
In all instances for subsequent re-decoration, use Firetex M71V2, Acrolon C137V2, Acrolon C237, Acrolon A7300 or Sher-Cryl M770 as appropriate
Please consult Rawlins technical 0113 2455450 (option 2) or send a message to [email protected] for detailed information.
Surface Preparation
Firetex FX2007 is designed for use over a suitably prepared and primed substrate
Ensure surfaces to be coated are clean, dry and free from all surface contamination
Under certain circumstances it may be possible to apply Firetex FX2007 directly to steel blast cleaned to a minimum standard of Sa2½ BS EN ISO 8501-1:2007, surface profile in the range 50-100 microns. Consult Rawlins Technical for further details
The details of airless spray tip orifice size, fan angle and pressure are given as a guide
Smaller fan angles should be used where the size of the work to be sprayed makes this appropriate
It may be found that slight variation in tip orifice size or pressure will provide optimum atomisation in some circumstances
In general, the operating pressure should be the lowest possible consistent with satisfactory atomisation
Recommended Equipment
Use 56:1 or 68:1 Graco King or equivalent Use 3/8” (9.53mm) ID fluid lines where lengths in excess of 3 metres are required. In-line gun or pump filters should not normally be used Maximum length of fluid line should not exceed 60 metres
For use on narrow web sections, the smallest tip recommended is a 21 thou (0.53mm ) with a 60 mesh pump filter
Application Conditions & Overcoating
This material should preferably be applied at temperatures in excess of 5ºC
In conditions of high relative humidity, ie 80-85% good ventilation conditions are essential
Substrate temperature shall be at least 3ºC above the dew point and always above 0°C
The application of Firetex FX2007 at elevated temperatures may reduce the sag resistance of the product
It is the responsibility of the applicator to determine what thickness of material can successfully be applied at the prevailing ambient temperature
The material must be protected from moisture during the drying period
Moisture ingress prior to drying may affect the integrity and fire protective properties of the coating
No more than 2 coats by airless spray should be applied within any 24 hour period
If the maximum recommended thickness per coat is exceeded or high film thicknesses are overcoated prematurely, cracking may occur
Firetex FX2007 is capable of withstanding external exposure without topcoat providing:
The product is allowed to dry for at least 24 hours at 15°C in dry conditions with good air movement and ventilation
These conditions are based on a total dry film thickness of up to 800 microns
The drying time required will be increased if the film thickness is greater than 800 microns
The substrate temperature is at least 3°C above the dew point at the time of application and during the drying period
Additional Notes
Maximum service temperature is 70°C. At temperatures greater than 40°C thermoplasticity may be observed
Dry Film Thickness Measurement
All DFT specifications quoted are mean values, measurements should be taken for I-Sections to the following recommendations:
Web – 2 per 100cm length
Flange – (upper, lower, inside and outside) – 1 per 100cm length
High dft’s and/or reduced temperatures will extend the drying time and hence the period when dft measurement can be carried out accurately
Small areas of mechanical damage can be repaired using Firetex M72, FX1007 or FX2007 as preferred
Larger areas of mechanical damage should be repaired using Firetex FX1007 or FX2007 as preferred, applied by brush or spray
All repairs should then have the original topcoat reinstated by brush or spray as required
Numerical values quoted for physical data may vary slightly from batch to batch
Maximum Allowable Dry Film Thickness
The values stated below are the maximum allowable measured mean dry film thicknesses for this product. If measured mean thicknesses are in excess of these values, measures need to be taken to reduce the measured thickness to below the maximum allowed:
3 sided I beam: 1,310μm (51.8 mil)
4 sided I beam: 1,310μm (51.8 mil)
4 sided I column: 1,423μm (56.0 mil)
CHS Column: 1,448μm (57.0 mil)
RHS Column: 1,448μm (57.0 mil)
3-sided RHS beam: 1,310μm (51.8 mil)
4-sided RHS beam: 1,310μm (51.8 mil)
IMPORTANT FIRE PRODUCTS NOTICE: The information displayed on this website should be used as a guide ONLY and our Technical Department should be contactedto obtain a tailored specification and any advice necessary before you place an order for fire protection products. Fire protection products are non-returnable except in accordance with Condition 8 of the Terms and Conditionsand should be applied only by an individual with the necessary expertise and experience.We will not be held liable for any resulting damage to property, human life or monetary costs incurred due to the incorrect specification you have prepared or use of fire protection products caused by your negligence, including your failure to have contacted us to obtain the relevant advice/specification.
Product Details
10447-987707
Data sheet
Manufacturer
Sherwin-Williams
For Use By
Industrial Use
Interior / Exterior Use
Interior & Exterior
For Use On
Structural Steel
Application Method
Spray
Sheen
Matt
Product Certifications
Tested and assessed to EN13381-8 and BS EN13381-9 CE Mark Number: 2812-CPR-GA5055 European Technical Assessment: ETA-22/0352 Certifire Approved - Certificate CF6088
Pack Size
20L
Recommended Thinner/Cleaner
Sherwin Williams No. 2
Shelf Life (from date of manufacture)
2 years
Recommended Dry Film Thickness
Flange – (upper, lower, inside and outside) – 1 per 100cm length
Customer agrees that before placing an Order, Customer has read and understood the most up to date Product Data Sheet for the Product. Where we have access to the Product Data Sheet from the manufacturer, we will either provide a copy on request, or include a link to the Product Data Sheet available on the manufacturer’s website. Customer further agrees that we have no liability for any errors or omissions contained within the Product Data Sheets. For more information, please see our Terms & Conditions of Sale.
Sherwin-Williams Firetex FX2007 is only available with the shipping and delivery timescales listed below - please do not contact our Customer Support Team with enquiries about alternative or earlier shipping and delivery times.
Saturdays and Sundays, as well as Bank Holidays, are not classed as working days.
Orders placed after the cut-off for this product will not be processed for earliest dispatch until 9am the next working day.
Sherwin-Williams Cleanser/Thinner No.2 is a specially formulated blend of solvents designed to mix with its compatible Sherwin-Williams products to create an optimal consistency for application whether it be for Brush, Roller or Spray. It can also be used for cleaning of surfaces and application equipment.
A high performance, fast drying acrylic urethane gloss finish in 450+ colours for use where long term exterior gloss and colour retention characteristics are required.Suitable for use as a final coat(s) in conjunction with epoxy or polyurethane based protective systems for new construction or maintenance purposes Please note: Also...
Sherwin-Williams Acrolon C237 (formerly Resistex C237) is a high performance fast drying acrylic urethane sheen finish for use where long term exterior colour retention characteristics are required. It is suitable for use as final coat or coats in conjunction with epoxy or polyurethane based protective systems for new construction or...
Sherwin-Williams Firetex M71V2 is a sheen decorative topcoat for the Firetex range of single pack intumescent coatings and also provides protection when used in internal semi-controlled conditions where condensation may occur (Category C2 as defined in ISO 12944-2).Available in 450+ colours Please note: Also available in Ready Mixed...
Sherwin-Williams Sher-Cryl M770 (formerly known as Envirogard M770) is a water based quick drying gloss finish or sealercoat for the entire Sherwin-Williams FX product range.Also available in 500+ RAL and British Standard coloursPlease see Sherwin-Williams Sher-Cryl M770 - Special ColoursPlease note: This product is subject to a...
Sherwin-Williams Acrolon 7300 is a high solids, tin free polyurethane, with fast drying and high gloss attributes. Acrolon 7300 can suitable for use where long term exterior gloss and colour retention characteristics are required. Gloss levels:Gloss: 70%+ Semi-Gloss - approx. 40% Available in 450+ coloursProfessional use only -...